Wire size calculator / Ampacity

Wire ampacity chart

Allowable current for copper and aluminum conductors at 60°C, 75°C, and 90°C, then the two multipliers that shrink those numbers in real installations.

Ampacity is the current a conductor can carry continuously without exceeding its temperature rating. The everyday table, NEC Table 310.16, is written for one specific installation: not more than three current-carrying conductors, in a raceway, cable, or direct burial, with 30°C (86°F) air around them. Use a different column and those assumptions no longer hold.

How to read the columns

Pick the column for the insulation on the conductor, not the column you wish you had. TW and UF are 60°C. THW, THWN, XHHW, and USE are 75°C. THHN, THWN-2, XHHW-2, and USE-2 are 90°C. NM-B cable is limited to the 60°C column even when the conductors inside are rated hotter. The full list of type letters lives in the code’s insulation table; the names above are the ones that show up on most reels.

The terminal on the breaker or the panel has its own limit. For equipment rated 100 A or less, or marked for 14 AWG through 1 AWG, unmarked terminals are treated as 60°C. Most modern breakers are marked 75°C, and then the 75°C column is the cap. Conductors over 100 A, or terminals marked for conductors larger than 1 AWG, are 75°C unless marked otherwise. A 90°C insulation is still useful: you may start the ambient and bundling math in the 90°C column, and you may not finish above the terminal column.

Allowable ampacity in amperes. Not more than three current-carrying conductors, 30°C ambient. Values follow NEC Table 310.16. A dash means that size is not listed for that metal and temperature.
Size Copper 60°C Copper 75°C Copper 90°C Aluminum 60°C Aluminum 75°C Aluminum 90°C 240.4(D) max breaker
18 AWG — — 14 — — — —
16 AWG — — 18 — — — —
14 AWG 15 20 25 — — — 15 Cu
12 AWG 20 25 30 15 20 25 20 Cu · 15 Al
10 AWG 30 35 40 25 30 35 30 Cu · 25 Al
8 AWG 40 50 55 35 40 45 —
6 AWG 55 65 75 40 50 55 —
4 AWG 70 85 95 55 65 75 —
3 AWG 85 100 115 65 75 85 —
2 AWG 95 115 130 75 90 100 —
1 AWG 110 130 145 85 100 115 —
1/0 AWG 125 150 170 100 120 135 —
2/0 AWG 145 175 195 115 135 150 —
3/0 AWG 165 200 225 130 155 175 —
4/0 AWG 195 230 260 150 180 205 —
250 kcmil 215 255 290 170 205 230 —
300 kcmil 240 285 320 195 230 260 —
350 kcmil 260 310 350 210 250 280 —
400 kcmil 280 335 380 225 270 305 —
500 kcmil 320 380 430 260 310 350 —
600 kcmil 350 420 475 285 340 385 —
700 kcmil 385 460 520 315 375 425 —
750 kcmil 400 475 535 320 385 435 —
800 kcmil 410 490 555 330 395 445 —
900 kcmil 435 520 585 355 425 480 —
1000 kcmil 455 545 615 375 445 500 —
1250 kcmil 495 590 665 405 485 545 —
1500 kcmil 525 625 705 435 520 585 —
1750 kcmil 545 650 735 455 545 615 —
2000 kcmil 555 665 750 470 560 630 —

Eighteen and 16 AWG appear in the 90°C copper column and are not general building-wire sizes. The calculator does not offer them for power circuits. Fourteen AWG aluminum is not listed. A dash in the chart means the same thing: no value, not zero.

Ambient temperature

Table 310.16 was calculated at 30°C. Hotter air leaves the conductor less room to shed heat, so the ampacity is multiplied by a factor that depends on the insulation rating. A 90°C conductor keeps more of its ampacity in a hot attic than a 60°C conductor does, which is why derating is allowed to start in the insulation column. The factors below are NEC Table 310.15(B)(1). A dash means that insulation is not listed at that ambient.

Ambient temperature correction factors based on 30°C, NEC Table 310.15(B)(1). Multiply the Table 310.16 ampacity by the factor for the insulation temperature. A dash means that insulation is not listed at that ambient.
Ambient60°C75°C90°C
10°C or less1.291.201.15
11–15°C1.221.151.12
16–20°C1.151.111.08
21–25°C1.081.051.04
26–30°C1.001.001.00
31–35°C0.910.940.96
36–40°C0.820.880.91
41–45°C0.710.820.87
46–50°C0.580.750.82
51–55°C0.410.670.76
56–60°C—0.580.71
61–65°C—0.470.65
66–70°C—0.330.58
71–75°C——0.50
76–80°C——0.41
81–85°C——0.29

More than three current-carrying conductors

Conductors bundled for more than 24 inches, without spacing, heat each other. Table 310.15(C)(1) gives the adjustment. Equipment grounding conductors are not counted. A neutral that carries only the unbalanced current of a linear single-phase multiwire circuit is not counted either. A neutral that carries the full current, including the neutral of a circuit with harmonic loads, is counted. The count is the total in the raceway or cable, including spares that are connected, not the number of circuits you remember pulling.

Adjustment for more than three current-carrying conductors, NEC Table 310.15(C)(1). Percent of the Table 310.16 ampacity after any ambient correction.
Current-carrying conductorsPercent of ampacity
1–3100%
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

The two factors multiply. Nine 12 AWG THHN conductors in a 40°C attic start at 30 A in the 90°C column. The bundling factor for seven to nine conductors is 0.70, and the 36–40°C factor for 90°C insulation is 0.91. That is 30 × 0.70 × 0.91 = 19.11 A, which is then capped by the terminal column if the cap is lower. Nineteen amperes does not support a 20 A circuit, so the raceway needs a larger conductor, fewer conductors, or a cooler path. Open that attic run in the calculator.

Small-conductor breaker limits

NEC 240.4(D) limits the overcurrent device, which is a different number from the table ampacity. Copper is limited to 15 A on 14 AWG, 20 A on 12 AWG, and 30 A on 10 AWG. Aluminum is limited to 15 A on 12 AWG and 25 A on 10 AWG. Twelve AWG copper at 75°C is a 25 A conductor in the ampacity table, and it still cannot be the only wire on a continuous 20 A load, because that load needs a 25 A device and 240.4(D) stops at 20 A. The code has exceptions for specific equipment. The calculator applies the general rule, and the checkbox on the form turns it off when you are working under one of those exceptions.

The chart is a planning reference, not a copy of the code book and not a substitute for it. Editions and local amendments differ. When the installation is not the ordinary raceway at 30°C, read the section that applies before you buy the wire. The wire size calculator applies this chart together with voltage drop.