American Wire Gauge is a geometric series. Each step changes the diameter, and the area that goes with a gauge is published in circular mils and in square millimetres. A circular mil is the area of a circle one mil (0.001 inch) across. The square-millimetre column in Table 8 is that area converted, not a suggestion to order “3.31 mm²” cable.
IEC 60228 sizes are nominal: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, and on up. Twelve AWG is 6,530 circular mils and 3.31 mm² exactly. The next IEC size at least that large is 4 mm². Four square millimetres is a different conductor, with its own maximum resistance. Using 4 mm² where a calculation called for 12 AWG is conservative on area. Using 2.5 mm² because it is “close” is not.
| Size | Circular mils | Exact mm² | Next IEC mm² | Diameter in | Copper Ω/kft | Aluminum Ω/kft |
|---|---|---|---|---|---|---|
| 18 AWG | 1,620 | 0.823 | 1.5 | 0.046 | 7.95 | 13.1 |
| 16 AWG | 2,580 | 1.31 | 1.5 | 0.058 | 4.99 | 8.21 |
| 14 AWG | 4,110 | 2.08 | 2.5 | 0.073 | 3.14 | 5.17 |
| 12 AWG | 6,530 | 3.31 | 4 | 0.092 | 1.98 | 3.25 |
| 10 AWG | 10,380 | 5.261 | 6 | 0.116 | 1.24 | 2.04 |
| 8 AWG | 16,510 | 8.367 | 10 | 0.146 | 0.778 | 1.28 |
| 6 AWG | 26,240 | 13.3 | 16 | 0.184 | 0.491 | 0.808 |
| 4 AWG | 41,740 | 21.15 | 25 | 0.232 | 0.308 | 0.508 |
| 3 AWG | 52,620 | 26.67 | 35 | 0.260 | 0.245 | 0.403 |
| 2 AWG | 66,360 | 33.62 | 35 | 0.292 | 0.194 | 0.319 |
| 1 AWG | 83,690 | 42.41 | 50 | 0.332 | 0.154 | 0.253 |
| 1/0 AWG | 105,600 | 53.49 | 70 | 0.372 | 0.122 | 0.201 |
| 2/0 AWG | 133,100 | 67.43 | 70 | 0.418 | 0.0967 | 0.159 |
| 3/0 AWG | 167,800 | 85.01 | 95 | 0.470 | 0.0766 | 0.126 |
| 4/0 AWG | 211,600 | 107.2 | 120 | 0.528 | 0.0608 | 0.1 |
| 250 kcmil | 250,000 | 127 | 150 | 0.575 | 0.0515 | 0.0847 |
| 300 kcmil | 300,000 | 152 | 185 | 0.630 | 0.0429 | 0.0707 |
| 350 kcmil | 350,000 | 177 | 185 | 0.681 | 0.0367 | 0.0605 |
| 400 kcmil | 400,000 | 203 | 240 | 0.728 | 0.0321 | 0.0529 |
| 500 kcmil | 500,000 | 253 | 300 | 0.813 | 0.0258 | 0.0424 |
| 600 kcmil | 600,000 | 304 | 400 | 0.893 | 0.0214 | 0.0353 |
| 700 kcmil | 700,000 | 355 | 400 | 0.964 | 0.0184 | 0.0303 |
| 750 kcmil | 750,000 | 380 | 400 | 0.998 | 0.0171 | 0.0282 |
| 800 kcmil | 800,000 | 405 | 500 | 1.030 | 0.0161 | 0.0265 |
| 900 kcmil | 900,000 | 456 | 500 | 1.094 | 0.0143 | 0.0235 |
| 1000 kcmil | 1,000,000 | 507 | 630 | 1.152 | 0.0129 | 0.0212 |
| 1250 kcmil | 1,250,000 | 633 | 800 | 1.289 | 0.0103 | 0.0169 |
| 1500 kcmil | 1,500,000 | 760 | 800 | 1.412 | 0.00858 | 0.0141 |
| 1750 kcmil | 1,750,000 | 887 | 1000 | 1.526 | 0.00735 | 0.0121 |
| 2000 kcmil | 2,000,000 | 1013 | — | 1.632 | 0.00643 | 0.0106 |
How the calculator uses each system
In AWG mode the wire size calculator selects from Table 310.16 and uses the Table 8 resistance of that exact size. The result also shows the exact square millimetres and the next IEC size at least that large, labeled as a translation rather than as the thing you must order.
In mm² mode it selects an IEC 60228 cross-section. Voltage drop uses the IEC maximum DC resistance at 20°C, corrected to 75°C with a coefficient of 0.00393 per degree for copper and 0.00403 for aluminum. Those coefficients are the 20°C form of the Table 8 note, which quotes 0.00323 and 0.00330 at 75°C. Ampacity is taken from the largest AWG or kcmil whose Table 8 area does not exceed the IEC size. Sixteen mm² sits between 6 AWG (13.3 mm²) and 4 AWG (21.15 mm²), so its ampacity is the 6 AWG value. That mapping is conservative, and it is stated on the result because the NEC does not list metric building wire.
Resistance columns
The ohms per 1,000 feet are for stranded, uncoated conductors at 75°C. Coated (tinned) copper runs a few percent higher, and solid 14 through 8 AWG runs a little lower, because the strands of a Class B conductor take a longer path than the cable. Compact stranding changes the diameter, not the job of this chart. For a voltage-drop number on a size you already have, use the voltage drop calculator. For the current the same size may carry, use the ampacity chart.