Wire size calculator / 12 AWG ampacity

How many amps can 12 gauge wire carry?

NEC Table 310.16 listings for 12 AWG, the selected small-conductor note when this tool has one, and a Chapter 9 Table 8 voltage-drop example. Not a breaker schedule.

Twelve AWG has hotter copper cells above its selected small-conductor ceiling. Reading a hotter cell as permission to load the branch to that cell can overlook the separate overcurrent limit. The ceiling stays on the ordinary overcurrent device. The hotter cell can still be the place correction starts, before a terminal or cable cap pulls the result back down.

Aluminum is listed at twelve gauge, with its own lower cells and its own selected ceiling. A copper habit does not transfer to that metal. The equipment’s conductor-material marking and the specified torque decide whether aluminum is eligible at all. Voltage drop on a 120 V run is still calculated from the stranded resistance, not from the breaker slogan.

The example current of 20 A equals the copper listing at 60°C. The prefilled calculator uses 120 V, 60 ft one way, 60°C insulation, and 60°C terminals. Those are inputs, not a required circuit.

The selected NEC 240.4(D) ceilings in this tool are copper 20 A and aluminum 15 A. Those are ordinary overcurrent-device limits, not extra ampacity, and they are not a complete breaker-selection procedure. Equipment exceptions are not checked.

Aluminum 12 AWG is listed at 15 A (60°C), 20 A (75°C), and 25 A (90°C), against copper 20 A, 25 A, and 30 A. Stranded resistance at 75°C is 3.25 Ω/kft aluminum and 1.98 Ω/kft copper. The same label is not the same conductor. Some equipment permits copper only.

Table 8 also lists solid copper 1.93 Ω/kft and solid aluminum 3.18 Ω/kft beside stranded copper 1.98 Ω/kft and stranded aluminum 3.25 Ω/kft. The calculator’s sizing path uses the stranded column.

Table 8 lists 7 strands and 6530 circular mils for 12 AWG. The rounded nominal area is 3.31 mm². Bare stranded diameter is 0.092 in, which excludes insulation and is not conduit fill.

12 AWG from NEC Table 310.16 (30°C ambient, not more than three current-carrying conductors) and Chapter 9 Table 8 at 75°C. A dash means no listing. Bare diameter excludes insulation.
ListingCopperAluminum
60°C ampacity (A)2015
75°C ampacity (A)2520
90°C ampacity (A)3025
Stranded Ω/kft1.983.25
Solid Ω/kft1.933.18
Selected 240.4(D) ceiling (A)2015
Circular mils6530
Rounded mm²3.31
Strands7
Bare diameter (in)0.092

For 12 AWG itself, not for whatever size the calculator recommends, Table 8 stranded copper resistance of 1.98 Ω/kft at 75°C gives 4.75 V (3.96% of 120 V) using 2 × I × R × L / 1,000. Reactance is omitted. Displayed volts are rounded to two decimals. The same inputs with stranded aluminum resistance 3.25 Ω/kft give 7.80 V (6.50%). If that percentage is outside the prefilled drop limit, the calculator will name a different size. That is the voltage-drop check, not a second ampacity table.

From 14 AWG to 12 AWG, the 75°C copper listing goes from 20 A to 25 A. Stranded copper resistance at 75°C goes from 3.14 Ω/kft to 1.98 Ω/kft.

From 12 AWG to 10 AWG, the 75°C copper listing goes from 25 A to 35 A. Stranded copper resistance at 75°C goes from 1.98 Ω/kft to 1.24 Ω/kft.

Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.

Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.

Related guides

Open the wire size calculator · Ampacity chart · Voltage drop calculator · Printable chart

Check an example against 12 AWG

The form starts from this page’s example. The address stays on this guide until you edit a field. After an edit, a shared link includes those settings in the URL, and opening that link sends the URL to the host.

Circuit

Headline metal

Both metals are compared. Verify equipment compatibility; some equipment permits copper only.

System

General NEC notes suggest 3% on a branch or feeder and 5% combined. Special equipment and local codes may require other limits; upstream drop is not included.

Estimated size

Enter the load current and the one-way distance. The size appears here, with the limit that set it.

Temperature and bundling

These conditions affect the table ampacity used for the comparison.

Conductor insulation

Use the rating marked for wet or dry conditions. THHN is 90°C dry; XHHW is 90°C dry or 75°C wet. For NM-B use 90°C insulation and a 60°C cap below.

Terminal / cable ampacity cap

Use the lowest applicable rating at either end, including cable limits. The general unmarked default is 60°C for equipment rated ≤100 A or marked for 14–1 AWG. Confirm equipment markings before selecting 75°C; NM-B remains capped at 60°C.

Equipment grounding conductors are excluded. Verify neutrals, harmonic loads, and all other current-carrying conductors in the raceway or cable; the automatic count does not check these.

AC impedance (Chapter 9 Table 9)

At power factor 1, the reactance term is zero, but Table 9 AC resistance still applies. Unlisted sizes have no Table 9 result.

Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.

Questions

How many amps can 12 gauge wire carry?

12 AWG copper in NEC Table 310.16 is listed at 20 A at 60°C, 25 A at 75°C, and 30 A at 90°C. Aluminum 12 AWG is listed at 15 A (60°C), 20 A (75°C), and 25 A (90°C), against copper 20 A, 25 A, and 30 A. Stranded resistance at 75°C is 3.25 Ω/kft aluminum and 1.98 Ω/kft copper. The same label is not the same conductor. Some equipment permits copper only. Those cells assume not more than three current-carrying conductors and 30°C ambient. They are not a breaker size by themselves. The selected NEC 240.4(D) ceilings in this tool are copper 20 A and aluminum 15 A. Those are ordinary overcurrent-device limits, not extra ampacity, and they are not a complete breaker-selection procedure. Equipment exceptions are not checked. Planning estimate only. Consult local code and a qualified electrician.

Does a hotter temperature column raise the breaker for 12 AWG?

The selected copper ceiling is 20 A. The selected aluminum ceiling is 15 A. That ceiling limits the ordinary overcurrent device. A higher Table 310.16 cell does not lift it. This is not a complete breaker-selection procedure. Planning estimate only. Consult local code and a qualified electrician.

What voltage drop does 12 AWG have on the example?

For 12 AWG itself, not for whatever size the calculator recommends, Table 8 stranded copper resistance of 1.98 Ω/kft at 75°C gives 4.75 V (3.96% of 120 V) using 2 × I × R × L / 1,000. Reactance is omitted. Displayed volts are rounded to two decimals. The same inputs with stranded aluminum resistance 3.25 Ω/kft give 7.80 V (6.50%). If that percentage is outside the prefilled drop limit, the calculator will name a different size. That is the voltage-drop check, not a second ampacity table.

Why can the 75°C copper cell be higher than the breaker ceiling?

The temperature cell is an ampacity listing. The selected small-conductor ceiling is an overcurrent-device limit for the ordinary case. This tool keeps them separate. A higher listing does not lift the ceiling, and disabling the ceiling in the calculator does not prove that an equipment exception applies.