Copper and aluminum rows that share an AWG label do not share an ampacity or a resistance. Aluminum’s stranded resistance is higher and its table ampacity is lower where both are listed. This page divides those two resistance cells so you can see the ratio move. The quotient is a description of that row. It is not the illustrative K factor this project refuses to use for sizing, and it is not a conversion you can apply to the next size.
Nothing in the ratio establishes equipment compatibility. Follow the conductor-material marking and the torque instruction. A lug rated for a hotter temperature does not, by itself, approve aluminum. If the aluminum ampacity cell is a dash, stop. Do not borrow the copper cell.
| Size | Cu 75°C (A) | Al 75°C (A) | Cu Ω/kft | Al Ω/kft | Al/Cu resistance |
|---|---|---|---|---|---|
| 14 AWG | 20 | — | 3.14 | 5.17 | 1.65 |
| 12 AWG | 25 | 20 | 1.98 | 3.25 | 1.64 |
| 10 AWG | 35 | 30 | 1.24 | 2.04 | 1.65 |
| 8 AWG | 50 | 40 | 0.778 | 1.28 | 1.65 |
| 6 AWG | 65 | 50 | 0.491 | 0.808 | 1.65 |
| 4 AWG | 85 | 65 | 0.308 | 0.508 | 1.65 |
| 3 AWG | 100 | 75 | 0.245 | 0.403 | 1.64 |
| 2 AWG | 115 | 90 | 0.194 | 0.319 | 1.64 |
| 1 AWG | 130 | 100 | 0.154 | 0.253 | 1.64 |
| 1/0 AWG | 150 | 120 | 0.122 | 0.201 | 1.65 |
| 2/0 AWG | 175 | 135 | 0.0967 | 0.159 | 1.64 |
| 3/0 AWG | 200 | 155 | 0.0766 | 0.126 | 1.64 |
| 4/0 AWG | 230 | 180 | 0.0608 | 0.1 | 1.64 |
One worked drop, two metals
The home page’s 120 V, 20 A, 100 ft illustration uses Table 8 at 75°C. 12 AWG stranded copper (1.98 Ω/kft) drops 7.92 V (6.60%). 6 AWG stranded aluminum (0.808 Ω/kft) drops 3.23 V (2.69%). These are two conductors under one hypothetical load, not a statement that they are interchangeable. Reactance is omitted.
Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.
Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.