This sheet is a reference, not a second calculator. The ampacity half is the audited Table 310.16 cells, including the selected 14–10 AWG overcurrent ceilings this tool knows about. The resistance half is Table 8, stranded and solid where the row has a solid value. The volt columns beside the resistance are arithmetic at 1 A and 100 ft so a large conductor does not round to zero volts. They are useless as a shopping list: a 14 AWG row at 1 A is not permission to load 14 AWG to any current you later multiply.
Ambient correction, bundling, terminal temperature, continuous loads, and equipment listings are not baked into the cells. The ampacity chart page carries the factor tables. The calculator applies a specific circuit. Print the sheet, then do that other work. Local amendments can differ from the edition these cells were checked against.
Ampacity
| Size | Cu 60°C | Cu 75°C | Cu 90°C | Al 60°C | Al 75°C | Al 90°C | Selected 240.4(D) |
|---|---|---|---|---|---|---|---|
| 18 AWG | — | — | 14 | — | — | — | — |
| 16 AWG | — | — | 18 | — | — | — | — |
| 14 AWG | 15 | 20 | 25 | — | — | — | 15 Cu |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 | 20 Cu · 15 Al |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 | 30 Cu · 25 Al |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 | — |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 | — |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 | — |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 | — |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 | — |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 | — |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 | — |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 | — |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 | — |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 | — |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 | — |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 | — |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 | — |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 | — |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 | — |
| 600 kcmil | 350 | 420 | 475 | 285 | 340 | 385 | — |
| 700 kcmil | 385 | 460 | 520 | 315 | 375 | 425 | — |
| 750 kcmil | 400 | 475 | 535 | 320 | 385 | 435 | — |
| 800 kcmil | 410 | 490 | 555 | 330 | 395 | 445 | — |
| 900 kcmil | 435 | 520 | 585 | 355 | 425 | 480 | — |
| 1000 kcmil | 455 | 545 | 615 | 375 | 445 | 500 | — |
| 1250 kcmil | 495 | 590 | 665 | 405 | 485 | 545 | — |
| 1500 kcmil | 525 | 625 | 705 | 435 | 520 | 585 | — |
| 1750 kcmil | 545 | 650 | 735 | 455 | 545 | 615 | — |
| 2000 kcmil | 555 | 665 | 750 | 470 | 560 | 630 | — |
Resistance and calculated voltage drop
| Size | Cu stranded Ω/kft | Al stranded Ω/kft | Cu solid Ω/kft | Al solid Ω/kft | Cu 1φ/DC V | Al 1φ/DC V | Cu 3φ V | Al 3φ V |
|---|---|---|---|---|---|---|---|---|
| 18 AWG | 7.95 | 13.1 | 7.77 | 12.8 | 1.59 | 2.62 | 1.38 | 2.27 |
| 16 AWG | 4.99 | 8.21 | 4.89 | 8.05 | 0.998 | 1.64 | 0.864 | 1.42 |
| 14 AWG | 3.14 | 5.17 | 3.07 | 5.06 | 0.628 | 1.03 | 0.544 | 0.895 |
| 12 AWG | 1.98 | 3.25 | 1.93 | 3.18 | 0.396 | 0.650 | 0.343 | 0.563 |
| 10 AWG | 1.24 | 2.04 | 1.21 | 2 | 0.248 | 0.408 | 0.215 | 0.353 |
| 8 AWG | 0.778 | 1.28 | 0.764 | 1.26 | 0.156 | 0.256 | 0.135 | 0.222 |
| 6 AWG | 0.491 | 0.808 | — | — | 0.0982 | 0.162 | 0.0850 | 0.140 |
| 4 AWG | 0.308 | 0.508 | — | — | 0.0616 | 0.102 | 0.0533 | 0.0880 |
| 3 AWG | 0.245 | 0.403 | — | — | 0.0490 | 0.0806 | 0.0424 | 0.0698 |
| 2 AWG | 0.194 | 0.319 | — | — | 0.0388 | 0.0638 | 0.0336 | 0.0553 |
| 1 AWG | 0.154 | 0.253 | — | — | 0.0308 | 0.0506 | 0.0267 | 0.0438 |
| 1/0 AWG | 0.122 | 0.201 | — | — | 0.0244 | 0.0402 | 0.0211 | 0.0348 |
| 2/0 AWG | 0.0967 | 0.159 | — | — | 0.0193 | 0.0318 | 0.0167 | 0.0275 |
| 3/0 AWG | 0.0766 | 0.126 | — | — | 0.0153 | 0.0252 | 0.0133 | 0.0218 |
| 4/0 AWG | 0.0608 | 0.1 | — | — | 0.0122 | 0.0200 | 0.0105 | 0.0173 |
| 250 kcmil | 0.0515 | 0.0847 | — | — | 0.0103 | 0.0169 | 0.0089 | 0.0147 |
| 300 kcmil | 0.0429 | 0.0707 | — | — | 0.0086 | 0.0141 | 0.0074 | 0.0122 |
| 350 kcmil | 0.0367 | 0.0605 | — | — | 0.0073 | 0.0121 | 0.0064 | 0.0105 |
| 400 kcmil | 0.0321 | 0.0529 | — | — | 0.0064 | 0.0106 | 0.0056 | 0.0092 |
| 500 kcmil | 0.0258 | 0.0424 | — | — | 0.0052 | 0.0085 | 0.0045 | 0.0073 |
| 600 kcmil | 0.0214 | 0.0353 | — | — | 0.0043 | 0.0071 | 0.0037 | 0.0061 |
| 700 kcmil | 0.0184 | 0.0303 | — | — | 0.0037 | 0.0061 | 0.0032 | 0.0052 |
| 750 kcmil | 0.0171 | 0.0282 | — | — | 0.0034 | 0.0056 | 0.0030 | 0.0049 |
| 800 kcmil | 0.0161 | 0.0265 | — | — | 0.0032 | 0.0053 | 0.0028 | 0.0046 |
| 900 kcmil | 0.0143 | 0.0235 | — | — | 0.0029 | 0.0047 | 0.0025 | 0.0041 |
| 1000 kcmil | 0.0129 | 0.0212 | — | — | 0.0026 | 0.0042 | 0.0022 | 0.0037 |
| 1250 kcmil | 0.0103 | 0.0169 | — | — | 0.0021 | 0.0034 | 0.0018 | 0.0029 |
| 1500 kcmil | 0.00858 | 0.0141 | — | — | 0.0017 | 0.0028 | 0.0015 | 0.0024 |
| 1750 kcmil | 0.00735 | 0.0121 | — | — | 0.0015 | 0.0024 | 0.0013 | 0.0021 |
| 2000 kcmil | 0.00643 | 0.0106 | — | — | 0.0013 | 0.0021 | 0.0011 | 0.0018 |
Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.
Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.