Wire size calculator / Printable AWG chart

Printable AWG ampacity, resistance, and voltage-drop chart

Two tables for the bench or a PDF. Ampacity and resistance are the stored NEC cells. The voltage-drop columns are calculated from Table 8.

This sheet is a reference, not a second calculator. The ampacity half is the audited Table 310.16 cells, including the selected 14–10 AWG overcurrent ceilings this tool knows about. The resistance half is Table 8, stranded and solid where the row has a solid value. The volt columns beside the resistance are arithmetic at 1 A and 100 ft so a large conductor does not round to zero volts. They are useless as a shopping list: a 14 AWG row at 1 A is not permission to load 14 AWG to any current you later multiply.

Ambient correction, bundling, terminal temperature, continuous loads, and equipment listings are not baked into the cells. The ampacity chart page carries the factor tables. The calculator applies a specific circuit. Print the sheet, then do that other work. Local amendments can differ from the edition these cells were checked against.

Ampacity

Resistance and calculated voltage drop

Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.

Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.

Questions

Are the voltage-drop columns an NEC table?

No. Ampacity is NEC Table 310.16. Resistance is Chapter 9 Table 8 at 75°C. The volt columns are calculated for 1 A and 100 one-way feet from the stranded resistance, using 2 × I × R × L / 1,000 for single-phase or DC and √3 for balanced three-phase. Reactance is omitted. Multiply by the real current and by the one-way length in hundreds of feet. They are not an allowable-load table.

Do these ampacity numbers include attic temperature or a full conduit?

No. The ampacity columns are the base table: 30°C ambient and not more than three current-carrying conductors. Other conditions use the correction and adjustment tables on the ampacity chart. A dash is a missing listing, not zero, and a dash in the small-conductor column is not permission to omit overcurrent protection.

How do I save this chart as a PDF?

Use Print / Save as PDF. The button opens the browser’s print dialog on this device and does not upload the page to a server. Choose Save as PDF, or a printer, in that dialog. Landscape letter paper fits the columns more comfortably. The on-screen navigation is omitted from the printout. Planning estimate only. Consult local code and a qualified electrician.