A 240 V circuit does not get a new ampacity table. NEC Table 310.16 lists copper and aluminum by size and temperature, for not more than three current-carrying conductors at 30°C ambient. Voltage is not one of those columns. What voltage changes is the meaning of a volt of drop: percent drop is the volt drop divided by the source voltage.
The general NEC informational notes still talk about 3 percent on a branch or feeder and 5 percent combined. Those notes are not mandatory rules everywhere. Local and energy codes can impose their own limits, and this calculator does not include upstream feeder drop. The prefilled form uses the same 3 percent assumption as the home calculator until you change it.
10 AWG stranded copper resistance is 1.24 Ω/kft at 75°C. At 30 A and 100 ft one way, the single-phase Table 8 model (2 × I × R × L / 1,000, reactance omitted) gives 7.44 V (3.10%) on 240 V and 7.44 V (6.20%) on 120 V. The volt drop matches, so the 120 V percentage is twice the 240 V percentage in this example. Displayed volts are rounded to two decimals. This is the drop of that gauge, not a finding that the gauge is large enough.
What the calculator does with three different inputs
Each row is the home calculator’s 30 A example, or that example with the length or the voltage changed. Insulation, terminals, ambient, and conductor count stay on the preset. The estimate is whatever single conductor passes both checks. It is not an appliance installation.
| Example | Assumptions | Copper estimate | Aluminum estimate |
|---|---|---|---|
| 30 A example at the preset length | 240 V single-phase, 30 A noncontinuous, 40 ft one way, 3% drop limit, 75°C insulation, 60°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 10 AWG (Ampacity governs) | 8 AWG (Ampacity governs) |
| 30 A at 100 ft | 240 V single-phase, 30 A noncontinuous, 100 ft one way, 3% drop limit, 75°C insulation, 60°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 8 AWG (Voltage drop governs) | 6 AWG (Voltage drop governs) |
| 30 A at 120 V and 100 ft | 120 V single-phase, 30 A noncontinuous, 100 ft one way, 3% drop limit, 75°C insulation, 60°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 6 AWG (Voltage drop governs) | 4 AWG (Voltage drop governs) |
30 A example at the preset length, copper. Voltage drop would allow 12 AWG. 12 AWG exceeds the NEC 240.4(D) small-conductor breaker limit for this load, so 10 AWG is required. Ampacity governs.
30 A example at the preset length, aluminum. Voltage drop would allow 10 AWG. 10 AWG exceeds the NEC 240.4(D) small-conductor breaker limit for this load, so 8 AWG is required. Ampacity governs.
30 A at 100 ft, copper. Ampacity would allow 10 AWG. Voltage drop requires 8 AWG, so voltage drop governs.
30 A at 100 ft, aluminum. Ampacity would allow 8 AWG. Voltage drop requires 6 AWG, so voltage drop governs.
30 A at 120 V and 100 ft, copper. Ampacity would allow 10 AWG. Voltage drop requires 6 AWG, so voltage drop governs.
30 A at 120 V and 100 ft, aluminum. Ampacity would allow 8 AWG. Voltage drop requires 4 AWG, so voltage drop governs.
Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.
Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.