Level 2 charging is discussed here as a 240 V example because that is the voltage on the calculator’s 48 A continuous preset. The nameplate and the installation manual control the real voltage, the real continuous current, and the conductor metal. The Article 625 section numbers below follow the 2017/2023 NEC sources used here; check the locally adopted edition. This page does not design an EV installation, pick a breaker, or apply equipment-specific rules beyond the calculator’s general checks.
NEC 625.42 treats EV charging loads as continuous, regardless of charging duration. The general three-hour definition does not exempt a shorter charging session. This guide’s calculator keeps the continuous-load check enabled, including when a shared URL requests otherwise. There is no mixed-load line. The pre-adjustment conductor check uses 125 percent of the entered current against the terminal column; adjusted ampacity and voltage drop use actual current. NEC 625.41 separately requires overcurrent protection rated at least 125 percent of the equipment’s maximum load. The calculator does not choose that device.
The 40 A, 48 A and 50 A labels are charging currents, not breaker ratings. Their 125 percent values are 50 A, 60 A and 62.5 A respectively. A 50 A charging current must not be treated as a 50 A circuit. Confirm the equipment’s allowed circuit rating and installation instructions. A 75°C terminal row requires identified equipment; the general unmarked case for smaller equipment is 60°C. For NM-B cable the ampacity cap stays at 60°C even with 75°C equipment. The last row keeps the 48 A preset and changes only the terminal/cable cap.
Tesla’s Gen 3 Wall Connector manual, printed p. 7 illustrates the distinction: 48 A output uses a 60 A circuit, copper terminations only, and at least 6 AWG copper with 75°C equipment or 4 AWG with a 60°C breaker, using the specified 90°C THWN-2 conductors. These are that product’s instructions, not universal charger specifications. Southwire’s NM-B specifications confirm the 60°C ampacity limit.
40 A continuous is checked at 50 A before correction; 48 A continuous is checked at 60 A before correction; 50 A continuous is checked at 62.5 A before correction. Those products are the calculator’s continuous-load check, not a table of charger wire sizes.
Estimates under stated assumptions
Changing the length, the drop limit, or the terminal rating changes the result. Do not copy a gauge off this table without the assumptions beside it. Aluminum results are table comparisons, not permission to land aluminum conductors.
| Example | Assumptions | Copper estimate | Aluminum estimate |
|---|---|---|---|
| 40 A continuous | 240 V single-phase, 40 A continuous, 50 ft one way, 3% drop limit, 90°C insulation, 75°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 8 AWG (Ampacity governs) | 6 AWG (Ampacity governs) |
| 48 A continuous | 240 V single-phase, 48 A continuous, 75 ft one way, 3% drop limit, 90°C insulation, 75°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 6 AWG (Ampacity governs) | 4 AWG (Ampacity governs) |
| 50 A continuous | 240 V single-phase, 50 A continuous, 50 ft one way, 3% drop limit, 90°C insulation, 75°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 6 AWG (Ampacity governs) | 4 AWG (Ampacity governs) |
| 48 A continuous, 60°C terminals | 240 V single-phase, 48 A continuous, 75 ft one way, 3% drop limit, 90°C insulation, 60°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 4 AWG (Ampacity governs) | 3 AWG (Ampacity governs) |
40 A continuous, copper. Voltage drop would allow 10 AWG. 10 AWG exceeds the NEC 240.4(D) small-conductor breaker limit for this load, so 8 AWG is required. Ampacity governs.
40 A continuous, aluminum. Voltage drop would allow 8 AWG. Ampacity requires 6 AWG, so ampacity governs.
48 A continuous, copper. Voltage drop would allow 8 AWG. Ampacity requires 6 AWG, so ampacity governs.
48 A continuous, aluminum. Voltage drop would allow 6 AWG. Ampacity requires 4 AWG, so ampacity governs.
50 A continuous, copper. Voltage drop would allow 10 AWG. Ampacity requires 6 AWG, so ampacity governs.
50 A continuous, aluminum. Voltage drop would allow 8 AWG. Ampacity requires 4 AWG, so ampacity governs.
48 A continuous, 60°C terminals, copper. Voltage drop would allow 8 AWG. Ampacity requires 4 AWG, so ampacity governs.
48 A continuous, 60°C terminals, aluminum. Voltage drop would allow 6 AWG. Ampacity requires 3 AWG, so ampacity governs.
Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.
Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.