Four AWG is a clean label for comparing the two metals, because neither side is missing a temperature cell and neither side sits in the selected small-conductor column. Aluminum’s cells are lower and its resistance cell is higher. If you divide the two stranded resistance cells you get this row’s ratio only. The next size will not repeat that ratio, and this project does not carry a universal aluminum constant for inventing ratings.
Strand count in this Table 8 row is still in the seven-strand group used by the smaller building sizes. Area is the table’s rounded nominal square millimetres. A nearby IEC nominal size is a numerical comparison on the AWG-to-mm² page, not permission to substitute a cable or to borrow this ampacity.
The example current of 65 A does not equal any copper temperature cell for 4 AWG. The prefilled calculator uses 240 V, 100 ft one way, 75°C insulation, and 75°C terminals. Those are inputs, not a required circuit.
The selected NEC 240.4(D) column in this tool has no special ceiling for 4 AWG. A blank is not permission to omit overcurrent protection. Table ampacity, the terminal cap, and voltage drop still apply.
Aluminum 4 AWG is listed at 55 A (60°C), 65 A (75°C), and 75 A (90°C), against copper 70 A, 85 A, and 95 A. Stranded resistance at 75°C is 0.508 Ω/kft aluminum and 0.308 Ω/kft copper. The same label is not the same conductor. Some equipment permits copper only.
This chart’s Table 8 row for 4 AWG publishes stranded resistance only (0.308 Ω/kft copper, 0.508 Ω/kft aluminum). The calculator uses that stranded value.
Table 8 lists 7 strands and 41740 circular mils for 4 AWG. The rounded nominal area is 21.15 mm². Bare stranded diameter is 0.232 in, which excludes insulation and is not conduit fill.
| Listing | Copper | Aluminum |
|---|---|---|
| 60°C ampacity (A) | 70 | 55 |
| 75°C ampacity (A) | 85 | 65 |
| 90°C ampacity (A) | 95 | 75 |
| Stranded Ω/kft | 0.308 | 0.508 |
| Solid Ω/kft | — | — |
| Selected 240.4(D) ceiling (A) | — | — |
| Circular mils | 41740 | |
| Rounded mm² | 21.15 | |
| Strands | 7 | |
| Bare diameter (in) | 0.232 | |
For 4 AWG itself, not for whatever size the calculator recommends, Table 8 stranded copper resistance of 0.308 Ω/kft at 75°C gives 4.00 V (1.67% of 240 V) using 2 × I × R × L / 1,000. Reactance is omitted. Displayed volts are rounded to two decimals. The same inputs with stranded aluminum resistance 0.508 Ω/kft give 6.60 V (2.75%). If that percentage is outside the prefilled drop limit, the calculator will name a different size. That is the voltage-drop check, not a second ampacity table.
From 6 AWG to 4 AWG, the 75°C copper listing goes from 65 A to 85 A. Stranded copper resistance at 75°C goes from 0.491 Ω/kft to 0.308 Ω/kft.
From 4 AWG to 3 AWG, the 75°C copper listing goes from 85 A to 100 A. Stranded copper resistance at 75°C goes from 0.308 Ω/kft to 0.245 Ω/kft.
Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.
Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.