A subpanel feeder is a load calculation, a terminal rating, a metal the equipment lists, a grounding and bonding scheme, and a length. This calculator does not do that design. The numbers 100 A and 200 A on this page are inputs, the same way any other current is an input. They are not standard answers.
Length is why a cell that matches the load can still be the wrong conductor. The 25 ft and 80 ft rows at 200 A and 75°C terminals produce the same copper and aluminum estimates (3/0 AWG (Ampacity governs) copper, 250 kcmil (Ampacity governs) aluminum). Between those lengths, voltage drop has not replaced the governing limit. A longer one-way run can still do that. A 60°C terminal row is included because the general unmarked rule for smaller equipment is not something to ignore just because the panel nameplate is large. Read the assumptions in the row before you read the gauge.
These rows assume the entire entered current is noncontinuous. A panel’s 100 A or 200 A rating is not a load calculation. NEC 215.2(A)(1) requires the applicable continuous-load allowance before correction and adjustment, and adequate ampacity for actual load after those factors. NEC 215.3 and Article 240 separately govern overcurrent protection. A mixed feeder needs its actual continuous and noncontinuous loads evaluated.
For a new 120/240 V feeder using a wire equipment grounding conductor, the usual arrangement is two ungrounded conductors, a neutral and an equipment grounding conductor. Keep neutral isolated from the subpanel enclosure and equipment grounding conductors downstream of the service disconnect (250.24(A)(5), 250.142(B)). A feeder to a separate building also requires the grounding electrode system in 250.32(A) and the equipment grounding path in 250.32(B); earth is not a substitute for that fault-return path. Neutral sizing, grounding conductor sizing, building disconnects and existing-installation exceptions are outside these estimates.
The whole-dwelling feeder allowance in NEC 310.12(B) requires a feeder supplying the entire load associated with an individual dwelling unit, along with the section’s other conditions. It is not a blanket reduction for an ordinary subpanel feeder. The separate feeder ampacity provision in 310.12(C) also needs review for an actual dwelling installation; neither provision is applied here. The older source edition calls these rules 310.15(B)(7). No dwelling reduction is applied in these rows.
Single-conductor estimates
The first row is the calculator’s 100 A example preset. Later rows change the terminal rating, the current, or the length and leave the other checks on their stated values. No row applies dwelling service options, demand factors, or parallel conductors.
| Example | Assumptions | Copper estimate | Aluminum estimate |
|---|---|---|---|
| 100 A, 60°C terminals | 240 V single-phase, 100 A noncontinuous, 80 ft one way, 3% drop limit, 75°C insulation, 60°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 1 AWG (Ampacity governs) | 1/0 AWG (Ampacity governs) |
| 100 A, 75°C terminals | 240 V single-phase, 100 A noncontinuous, 80 ft one way, 3% drop limit, 75°C insulation, 75°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 3 AWG (Ampacity governs) | 1 AWG (Ampacity governs) |
| 200 A, 75°C terminals, 80 ft | 240 V single-phase, 200 A noncontinuous, 80 ft one way, 3% drop limit, 75°C insulation, 75°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 3/0 AWG (Ampacity governs) | 250 kcmil (Ampacity governs) |
| 200 A, 75°C terminals, 25 ft | 240 V single-phase, 200 A noncontinuous, 25 ft one way, 3% drop limit, 75°C insulation, 75°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 3/0 AWG (Ampacity governs) | 250 kcmil (Ampacity governs) |
| 200 A, 60°C terminals, 80 ft | 240 V single-phase, 200 A noncontinuous, 80 ft one way, 3% drop limit, 75°C insulation, 60°C terminals, 30°C ambient, 2 current-carrying conductors, small-conductor check on, Table 8 resistance only | 250 kcmil (Ampacity governs) | 350 kcmil (Ampacity governs) |
100 A, 60°C terminals, copper. Voltage drop would allow 4 AWG. Ampacity requires 1 AWG, so ampacity governs.
100 A, 60°C terminals, aluminum. Voltage drop would allow 3 AWG. Ampacity requires 1/0 AWG, so ampacity governs.
100 A, 75°C terminals, copper. Voltage drop would allow 4 AWG. Ampacity requires 3 AWG, so ampacity governs.
100 A, 75°C terminals, aluminum. Voltage drop would allow 3 AWG. Ampacity requires 1 AWG, so ampacity governs.
200 A, 75°C terminals, 80 ft, copper. Voltage drop would allow 2 AWG. Ampacity requires 3/0 AWG, so ampacity governs.
200 A, 75°C terminals, 80 ft, aluminum. Voltage drop would allow 1/0 AWG. Ampacity requires 250 kcmil, so ampacity governs.
200 A, 75°C terminals, 25 ft, copper. Voltage drop would allow 6 AWG. Ampacity requires 3/0 AWG, so ampacity governs.
200 A, 75°C terminals, 25 ft, aluminum. Voltage drop would allow 4 AWG. Ampacity requires 250 kcmil, so ampacity governs.
200 A, 60°C terminals, 80 ft, copper. Voltage drop would allow 2 AWG. Ampacity requires 250 kcmil, so ampacity governs.
200 A, 60°C terminals, 80 ft, aluminum. Voltage drop would allow 1/0 AWG. Ampacity requires 350 kcmil, so ampacity governs.
Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.
Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.