Two-aught sits between one-aught and three-aught. The name adds a zero, which looks like a larger jump than the table sometimes is. The only honest comparison is the neighbor cells for ampacity and the neighbor stranded resistances, linked below. Do not scale from the count of zeros.
Resistance at this size is low enough that a short 240 V run can look effortless, which is when people stop checking drop. A detached building or a long feeder can still make drop the governing limit. This page gives you the 2/0 cells and a drop at one stated current. It does not design the feeder.
The example current of 150 A does not equal any copper temperature cell for 2/0 AWG. It is above the 60°C copper cell of 145 A, so a 60°C terminal cap does not cover this current before any other correction. The prefilled calculator uses 240 V, 150 ft one way, 75°C insulation, and 75°C terminals. Those are inputs, not a required circuit.
The selected NEC 240.4(D) column in this tool has no special ceiling for 2/0 AWG. A blank is not permission to omit overcurrent protection. Table ampacity, the terminal cap, and voltage drop still apply.
Aluminum 2/0 AWG is listed at 115 A (60°C), 135 A (75°C), and 150 A (90°C), against copper 145 A, 175 A, and 195 A. Stranded resistance at 75°C is 0.159 Ω/kft aluminum and 0.0967 Ω/kft copper. The same label is not the same conductor. Some equipment permits copper only.
This chart’s Table 8 row for 2/0 AWG publishes stranded resistance only (0.0967 Ω/kft copper, 0.159 Ω/kft aluminum). The calculator uses that stranded value.
Table 8 lists 19 strands and 133100 circular mils for 2/0 AWG. The rounded nominal area is 67.43 mm². Bare stranded diameter is 0.418 in, which excludes insulation and is not conduit fill.
| Listing | Copper | Aluminum |
|---|---|---|
| 60°C ampacity (A) | 145 | 115 |
| 75°C ampacity (A) | 175 | 135 |
| 90°C ampacity (A) | 195 | 150 |
| Stranded Ω/kft | 0.0967 | 0.159 |
| Solid Ω/kft | — | — |
| Selected 240.4(D) ceiling (A) | — | — |
| Circular mils | 133100 | |
| Rounded mm² | 67.43 | |
| Strands | 19 | |
| Bare diameter (in) | 0.418 | |
For 2/0 AWG itself, not for whatever size the calculator recommends, Table 8 stranded copper resistance of 0.0967 Ω/kft at 75°C gives 4.35 V (1.81% of 240 V) using 2 × I × R × L / 1,000. Reactance is omitted. Displayed volts are rounded to two decimals. The same inputs with stranded aluminum resistance 0.159 Ω/kft give 7.16 V (2.98%). If that percentage is outside the prefilled drop limit, the calculator will name a different size. That is the voltage-drop check, not a second ampacity table.
From 1/0 AWG to 2/0 AWG, the 75°C copper listing goes from 150 A to 175 A. Stranded copper resistance at 75°C goes from 0.122 Ω/kft to 0.0967 Ω/kft.
From 2/0 AWG to 3/0 AWG, the 75°C copper listing goes from 175 A to 200 A. Stranded copper resistance at 75°C goes from 0.0967 Ω/kft to 0.0766 Ω/kft.
Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.
Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.