At 12 V, a drop that would be a small share of a 120 V branch can be a large share of the source. The resistance model is the same Chapter 9 Table 8 stranded value at 75°C. DC uses the factor of two, out and back, on the one-way length. Reactance is not part of a DC estimate. This page is not a solar, battery, or charge-controller design.
PV source circuits, battery fault current, controller terminals, and temperature-corrected array current are outside this calculator. The presets labeled as 12 V, 24 V, and 48 V DC examples were renamed for that reason: they are hypothetical loads. Use them to see percentage drop. Do not use them as a wiring diagram.
Copper drop at the 12 V preset
Each row is 20 A DC at 12 V and 20 ft one way, using that gauge’s stranded copper resistance. The percent column is the drop divided by 12 V. A row can show a huge percentage and still be the wrong conductor for ampacity. Read both.
| Size | Cu Ω/kft | Drop | Percent of 12 V |
|---|---|---|---|
| 14 AWG | 3.14 | 2.51 V | 20.93% |
| 12 AWG | 1.98 | 1.58 V | 13.20% |
| 10 AWG | 1.24 | 0.99 V | 8.27% |
| 8 AWG | 0.778 | 0.62 V | 5.19% |
| 6 AWG | 0.491 | 0.39 V | 3.27% |
Same conductor, three source voltages
10 AWG copper at 20 A and 20 ft. Only the source voltage changes. Ampacity cells do not.
| Source | Drop | Percent |
|---|---|---|
| 12 V | 0.99 V | 8.27% |
| 24 V | 0.99 V | 4.13% |
| 48 V | 0.99 V | 2.07% |
Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.
Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.
Related guides
Open the wire size calculator · Ampacity chart · Voltage drop calculator · Printable chart