Wire size calculator / 14 AWG ampacity

How many amps can 14 gauge wire carry?

NEC Table 310.16 listings for 14 AWG, the selected small-conductor note when this tool has one, and a Chapter 9 Table 8 voltage-drop example. Not a breaker schedule.

Fourteen AWG is the smallest copper size this calculator offers for a general power circuit. A single breaker number cannot describe all three copper temperature cells and the separate small-conductor overcurrent ceiling. Those columns do different jobs. A hotter insulation listing does not, by itself, raise the ordinary device above that ceiling, and this page does not evaluate equipment exceptions.

Aluminum at this label has no ampacity cells at all. The blanks are empty listings, not a zero-amp conductor you can “round up.” Stranded aluminum resistance can still appear in the resistance table; a resistance without an ampacity listing is not an allowable aluminum size here. On a long low-voltage branch, voltage drop often becomes the reason a larger copper size shows up in the calculator even when the ampacity cell looked sufficient.

The example current of 15 A equals the copper listing at 60°C. The prefilled calculator uses 120 V, 50 ft one way, 60°C insulation, and 60°C terminals. Those are inputs, not a required circuit.

The selected NEC 240.4(D) ceilings in this tool are copper 15 A. Those are ordinary overcurrent-device limits, not extra ampacity, and they are not a complete breaker-selection procedure. Equipment exceptions are not checked.

Table 310.16 has no aluminum ampacity listing for 14 AWG. Stranded aluminum resistance is still published as 5.17 Ω/kft. A resistance without an ampacity listing is not an allowable aluminum conductor in this chart.

Table 8 also lists solid copper 3.07 Ω/kft and solid aluminum 5.06 Ω/kft beside stranded copper 3.14 Ω/kft and stranded aluminum 5.17 Ω/kft. The calculator’s sizing path uses the stranded column.

Table 8 lists 7 strands and 4110 circular mils for 14 AWG. The rounded nominal area is 2.08 mm². Bare stranded diameter is 0.073 in, which excludes insulation and is not conduit fill.

14 AWG from NEC Table 310.16 (30°C ambient, not more than three current-carrying conductors) and Chapter 9 Table 8 at 75°C. A dash means no listing. Bare diameter excludes insulation.
ListingCopperAluminum
60°C ampacity (A)15—
75°C ampacity (A)20—
90°C ampacity (A)25—
Stranded Ω/kft3.145.17
Solid Ω/kft3.075.06
Selected 240.4(D) ceiling (A)15—
Circular mils4110
Rounded mm²2.08
Strands7
Bare diameter (in)0.073

For 14 AWG itself, not for whatever size the calculator recommends, Table 8 stranded copper resistance of 3.14 Ω/kft at 75°C gives 4.71 V (3.92% of 120 V) using 2 × I × R × L / 1,000. Reactance is omitted. Displayed volts are rounded to two decimals. The same inputs with stranded aluminum resistance 5.17 Ω/kft give 7.75 V (6.46%). If that percentage is outside the prefilled drop limit, the calculator will name a different size. That is the voltage-drop check, not a second ampacity table.

From 14 AWG to 12 AWG, the 75°C copper listing goes from 20 A to 25 A. Stranded copper resistance at 75°C goes from 3.14 Ω/kft to 1.98 Ω/kft.

Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.

Sources for these cells: existing Table 310.16 numerical cells in NFPA’s public development record, pp. 142–143 (proposed changes are not treated as adopted code) and NFPA 70 (2017), Chapter 9 Table 8, printed p. 689, in a third-party-hosted copy. The same publication supplies 110.14 (terminals and aluminum), 210.19/215.2 (continuous loads), 240.4(D) (small conductors), 250.24/250.32 (grounding), and 625.41/625.42 (EV loads). Schneider Electric’s voltage-drop formulas support the arithmetic; Table 8 AC results here omit reactance and assume unity power factor. Resistance and geometry are construction- and temperature-specific. Adopted editions and local amendments can differ.

Related guides

Open the wire size calculator · Ampacity chart · Voltage drop calculator · Printable chart

Check an example against 14 AWG

The form starts from this page’s example. The address stays on this guide until you edit a field. After an edit, a shared link includes those settings in the URL, and opening that link sends the URL to the host.

Circuit

Headline metal

Both metals are compared. Verify equipment compatibility; some equipment permits copper only.

System

General NEC notes suggest 3% on a branch or feeder and 5% combined. Special equipment and local codes may require other limits; upstream drop is not included.

Estimated size

Enter the load current and the one-way distance. The size appears here, with the limit that set it.

Temperature and bundling

These conditions affect the table ampacity used for the comparison.

Conductor insulation

Use the rating marked for wet or dry conditions. THHN is 90°C dry; XHHW is 90°C dry or 75°C wet. For NM-B use 90°C insulation and a 60°C cap below.

Terminal / cable ampacity cap

Use the lowest applicable rating at either end, including cable limits. The general unmarked default is 60°C for equipment rated ≤100 A or marked for 14–1 AWG. Confirm equipment markings before selecting 75°C; NM-B remains capped at 60°C.

Equipment grounding conductors are excluded. Verify neutrals, harmonic loads, and all other current-carrying conductors in the raceway or cable; the automatic count does not check these.

AC impedance (Chapter 9 Table 9)

At power factor 1, the reactance term is zero, but Table 9 AC resistance still applies. Unlisted sizes have no Table 9 result.

Planning estimate only. Consult local code and a qualified electrician before buying wire or energizing a circuit. Presets are hypothetical loads; this tool does not design motor, PV, battery, appliance, or EV installations.

Questions

How many amps can 14 gauge wire carry?

14 AWG copper in NEC Table 310.16 is listed at 15 A at 60°C, 20 A at 75°C, and 25 A at 90°C. Table 310.16 has no aluminum ampacity listing for 14 AWG. Stranded aluminum resistance is still published as 5.17 Ω/kft. A resistance without an ampacity listing is not an allowable aluminum conductor in this chart. Those cells assume not more than three current-carrying conductors and 30°C ambient. They are not a breaker size by themselves. The selected NEC 240.4(D) ceilings in this tool are copper 15 A. Those are ordinary overcurrent-device limits, not extra ampacity, and they are not a complete breaker-selection procedure. Equipment exceptions are not checked. Planning estimate only. Consult local code and a qualified electrician.

Does a hotter temperature column raise the breaker for 14 AWG?

The selected copper ceiling is 15 A. There is no selected aluminum ceiling for this size in this tool. That ceiling limits the ordinary overcurrent device. A higher Table 310.16 cell does not lift it. This is not a complete breaker-selection procedure. Planning estimate only. Consult local code and a qualified electrician.

What voltage drop does 14 AWG have on the example?

For 14 AWG itself, not for whatever size the calculator recommends, Table 8 stranded copper resistance of 3.14 Ω/kft at 75°C gives 4.71 V (3.92% of 120 V) using 2 × I × R × L / 1,000. Reactance is omitted. Displayed volts are rounded to two decimals. The same inputs with stranded aluminum resistance 5.17 Ω/kft give 7.75 V (6.46%). If that percentage is outside the prefilled drop limit, the calculator will name a different size. That is the voltage-drop check, not a second ampacity table.

Why is there no aluminum ampacity for 14 AWG?

Table 310.16, as stored in this chart, has no aluminum cells for 14 AWG. Do not read the blank as zero amperes or as permission to use aluminum. The copper cells and the selected copper overcurrent ceiling are the listings this page can show. Equipment that requires copper is a separate instruction from the manufacturer.